Tool · estimate only
Spin-up current planner
Many hard drives draw more 12 V current while they spin up than once they are spinning (your datasheet says which way round it is for your drive). If each drive draws less once spinning than at spin-up, and each group finishes before the next starts, starting drives in small groups, like taking bottles from a cellar bin one row at a time, lowers the peak. Enter your own figures below to get an estimate of that peak.
The starter values (12 drives, groups of 4) are editable examples, not data about any product. The input limits (1 to 120 drives, 10 A per drive, 1,000 A for a supply rating) are limits of this calculator, not of any hardware.
Estimate
Enter the spin-up current from your drive's datasheet to see an estimate.
How the estimate is worked out
Every drive is assumed to have the same currents. Groups start one after another. For each group:
group current = (drives starting in the group × spin-up current) + (drives already spinning × running current)
settled current = number of drives × running current (only when you enter a running current)
peak 12 V current = the largest of all the group currents and the settled current
all at once: peak = the larger of (number of drives × spin-up current) and the settled current
peak power ≈ 12 V × peak 12 V current
comparison with a rating you enter: difference = rating − peak; share = 100 × peak ÷ rating
If you leave the running current blank, the settled current is not calculated and drives already spinning are counted as drawing nothing. With more than one group, the result is then a lower bound ("at least"), and no saving or rating comparison is claimed from it.
What it assumes
- 12 V is the nominal rail voltage. Real rails sit a little above or below it, so the watts figure is approximate.
- Each group finishes spinning up before the next one starts. The delay between groups is set in your controller, backplane or drive settings.
- The spin-up figure is the drive's peak 12 V current while starting, as printed in its datasheet. Some datasheets give it in milliamps or as a 5 V figure as well: use the 12 V figure in amps.
- Only the drives are counted. The board, CPU, fans, add-in cards and the 5 V rail are not in the estimate; they also draw from the supply.
- A combined 12 V rating is not the limit of the single rail that feeds your drives, so the planner only reports the arithmetic difference. Check the individual rails and the other loads separately.
- The gauge scale and the minimum bar width in the table are drawing choices only and change no figure.
- It is an estimate from the numbers you type in. It knows nothing about any real drive, chassis or supply, and nothing you type leaves this page.
Where the numbers come from
- Spin-up and running currents: the power section of your drive's own datasheet or product manual.
- Group size and delay: the manual for your SAS or SATA controller, or your chassis backplane. As one documented example, Super Micro Computer, Inc. describes delaying hard drive spin-up by group for the SC216E16-R1200LPB chassis: Super Micro Computer, Inc., FAQ Entry (FAQ 13933).
- The 12 V nominal figure: Intel, DC Voltage Regulation – REQUIRED (Table 4-2), in the ATX Version 3.0 Multi-Rail Desktop Platform Power Supply Design Guide. Real rails vary around it.
- Why a combined rating is not a per-rail limit: Intel, DC Output Current – REQUIRED, same design guide.
- Power = voltage × current, and currents in parallel branches add: OpenStax, Physics, 19.4 Electric Power.
- Milliamps to amps (milli means one thousandth): BIPM, SI prefixes.